Grafik: Logo Franzen Feuerschutztüren
Franzen Feuerschutztüren
Zechenring 23
D-41836 Hückelhoven

phone +49(0)2433/93919‑0

Franzen fire door class E

Double leaf fire door ES-2/60

Franzen fire door ES-2/60 "System Schröders"

Double-leaf fire door ES-2/60

CE-marking marked

Fire resistance

fire resistance period 60 minutes
tested according to EN 1634-1

Combinable with additional performance characteristics:

Resistance to positive and negative pressure
(optional)

up to 3.800 Pa according to DIN EN 12211

expert opinion no. 40-52/16.120
Flush with surface
(optional)

flush-mounted design FLAT

Explosion protection
(optional)
Logo ATEX For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for Franzen hinged doors (in German language) System Schröders (PDF)
Technical data
Dimensions
(rough building dimension)
width up to 3,100 mm
height up to 3,100 mm
area per leaf max. 3.9 m²
Door leaf

leaf thickness 68 mm to 69 mm - smooth double-walled
plate thickness 1.0 mm to 1.5 mm

  • thin rebate design
    • optional thick rebate design
    • insulating insert
      • optional insulation inlet full-face glued and pressed with cover plate
        thus particularly plane and smooth door leaf
Frame
  • frame-system "ZNG" with flush clipped in Thelesol® fire protection strips
  • (see installation variants)
  • corner frame
  • optional enclosing frame
  • optional block frame

with elastic rubber seal
(seal type depending on performance characteristic)

Glass inset
(optional)

glass dimensions and -form variable
(rectangular glass inset max. 800 mm x 800 mm)

minimum frieze width: 90 mm

  • optional with intermediate glass inset bars
  • optional with port-hole (ø approx. 450 mm clear view)

glass inset bars with concealed screw connection (for rectangular glass inset)

Hinges

per leaf 2/3-part KO door hinges
with patented easy-running bearings as easy running doors

Fittings active leaf
  • optional any approved handle set according to EN 1906 resp. EN 179
  • optional panic bar handle or push bar according to EN 1125
Locking active leaf

single locking according to EN 12209, depending on version multi-point locking
profile cylinder prepared (cylinder on-site)

fixed leaf

internal snap bolt (locking upwards)
depending on version, with locking upwards and downwards (rebate shoot bolt, shoot bolt lock)

securing pins at both leafs

  • optional panic locking according to EN 179 resp. EN 1125
Self-closing

both leafs with door closer according to DIN EN 1154 resp. EN 1155
with door closing sequence control according to EN1158

Installation
  • in masonry
  • in concrete
  • in aerated concrete
  • in mounting walls min. F60
  • in encased steel columns
  • optional blunt installation in soffit
  • approved for installation at great heights (installation not at floor level: height on one or both sides > 500 mm above ground level - e.g. as manhole door/flap) with lower fire and smoke seal - also thresholdless
Marking

CE-Zeichen marking for firedoors according to EN 16034

Optional
  • lock control
  • automated opening
  • motor locks ( also in 3-way locking)
  • powder coating in RAL colors
  • prison cell doors (special locking and food flap)
  • special solutions according to request and customer requirements

The information given refers to the usual configurations. Individual configurations may be required when combining different performance characteristics.

Our team will be happy to assist you with the individual planning of your requirements.

  • Feuerschutztür ES-2-60
    Franzen ES-2/60double-leaf fire door"System Schröders"

Downloads ES-2/60