Franzen fire doors

Fire resistance door Franzen ES-2/120 System Schröders

double leaf fire door ES-2/120

CE-marking marked with declaration of performance

Fire resistance

fire resistance period 120 minutes
tested according to EN 1634-1

combinable with additional performance characteristics
Resistance to positive and negative pressure
(optional)

up to 5.000 Pa according to DIN EN 12211

expert opinion no. 16-003037-PR01
Flush with surface
(optional)

flush-mounted design FLAT

Explosion protection
(optional)
For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for Franzen hinged doors (in German language) System Schröders (PDF) Logo ATEX
Potential equalisation
(optional)

according to DIN EN 50310, DIN VDE 0100-410 bzw. DIN VDE 0100-540


Technical data
Dimensions
(rough building dimension)
width up to 3,100 mm
height up to 3,100 mm
area per leaf max. 3.9 m²
Door leaf

leaf thickness 68 mm to 69 mm - smooth double-walled
plate thickness 1.0 mm to 1.5 mm
leaf weight 25 - 30 kg/m²

thin rebate design

insert
  • optional full-face glued and pressed with cover plate,
    thus particularly smooth and even door leaf

securing pins

Frame

corner frame

frame-system "ZNG"
with flush clipped in Thelesol® fire protection strips and elastic rubber seal

  • optional enclosing frame
  • optional block frame

with elastic rubber seal
(seal type depends on performance characteristics)

Glass inset
(optional)

glass dimensions and -form variable
(rectangular glass inset max. 800 mm x 800 mm)

minimum frieze width: 90 mm

  • optional with intermediate glass inset bars
  • optional with port-hole

glass inset bars with concealed screw connection (for rectangular glass inset)

Hinges

2/3-part KO door hinges
with patented easy-running bearings as easy running doors

  • optional door hinge with 3D adjustment
Fittings active leaf
  • optional any approved handle set according to EN 1906 resp. EN 179
  • optional panic bar handle or push bar according to EN 1125
Locking active leaf

single locking according to EN 12209, depending on version multi-point locking
profile cylinder prepared (cylinder on-site)

fixed leaf

internal snap bolt (locking upwards)
depending on version, with locking upwards and downwards (rebate shoot bolt, shoot bolt lock)

  • optional panic locking according to EN 179 resp. EN 1125
Self-closing

both leafs with door closer according to DIN EN 1154 resp. EN 1155
with door closing sequence control according to EN1158

Installation
  • in masonry
  • in concrete
  • in aerated concrete
  • in mounting walls min. F120
  • in encased steel columns
  • optional blunt installation in soffit
  • approved for installation at great heights (installation not at floor level: height on one or both sides > 500 mm above ground level - e.g. as manhole door/flap) with lower fire and smoke seal - also thresholdless
Marking

CE-Zeichen marking for firedoors according to EN 16034

Optional
  • lock control
  • automated opening
  • motor locks ( also in 3-way locking)
  • powder coating in RAL colors
  • prison cell doors (special locking and food flap)
  • special solutions according to request and customer requirements

The information given refers to the usual configurations. Individual configurations may be required when combining different performance characteristics.