Franzen fire doors

Fire resistance door Franzen EIS-11System Schröders

single leaf highly fire resistant steel door / flap EI2120-Sa4-C5

CE-marking marked with declaration of performance

Fire resistance

tested EI2120-Sa4 / E 120 / EW 60 according to EN 1634-1

test report WFRC 360408 according to EN 13501-2

  • as a gate according to DIN EN 13241
  • as an external door according to DIN EN 14351-1

combinable with additional performance characteristics
Smoke control
(optional)
S200 tested according to EN 1634-3
Thermal transmittance
(optional)

UD-value ≥ 2.7 W/(m²K) according to EN ISO 10077-1

Burglar resistance
(optional)

RC2 - classification report no. 45-47/22, PIV-Velbert
RC1 - classification report no. 212 24294, ift Rosenheim

according to DIN EN 1627 ff

Air tightness
(optional)

up to class 4 according to EN 12207 (± 600 Pa)
expert opinion no. 11-000082-PR01

Resistance to wind load
(optional)

up to class C5 according to EN 12210 (± 2,000 Pa)
expert opinion no. 11-000082-PR01

Watertightness
(optional)

up to class 8A according to EN 12208 (+ 450 Pa)
expert opinion no. 11-000082-PR01

Resistance to positive and negative pressure
(optional)

according to DIN EN 12211 (up to 5,000 Pa)
expert opinion no. 16-003037-PR01

Behavior between different climates
(optional)

class 2 (d + e) according to EN 12219 (deflection)

Ability to release
(optional)

according to DIN EN 16034
hold-open device according to DIN EN 14637

according to DIN EN 14351-1
proven for doors in escape and rescue routes

Flush with surface
(optional)

flush-mounted design FLAT

Explosion protection
(optional)
For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for Franzen hinged doors (in German language) System Schröders (PDF) Logo ATEX
Potential equalisation
(optional)

according to DIN EN 50310, DIN VDE 0100-410 bzw. DIN VDE 0100-540


Technical data
Dimensions
(rough building dimension)
width from 500 mm up to 1,400 mm
height from 750 mm up to 2,650 mm

deviating special sizes possible with corresponding individual proof under building law
Door leaf

leaf thickness 68 mm to 69 mm - smooth double-walled
plate thickness 1.0 mm to 1.5 mm

thin rebate design

insulating insert
  • optional full-face glued and pressed with cover plate,
    thus particularly smooth and even door leaf

Thelesol® 120 fire protection strips at the door edges

securing pins

Frame

corner frame

frame-system "ZNG"
with elastic rubber seal

  • optional enclosing frame
  • optional block frame
Floor seal

required for smoke control, acoustic performance, air tightness

  • optional lowerable floor seal RSI
  • optional time-delayed closing floor seal RSI-V
    (not for acoustic performance, increased airtightness, resistance to wind load, watertightness)
  • optional sliding seal / grinding seal
Hinges

2/3-part KO door hinges
with patented easy-running bearings as easy running doors

  • optional door hinge with 3D adjustment
  • heavy-duty hinges available on request
Fittings
  • optional any approved handle set according to EN 1906 resp. EN 179
  • optional panic bar handle or push bar according to EN 1125
Locking

single locking according to EN 12209, depending on version multi-point locking
profile cylinder prepared (cylinder on-site)

  • optional panic locking according to EN 179 resp. EN 1125
Self-closing

door closer according to DIN EN 1154

  • optional spring hinge for smaller doors / flaps
Installation
  • in masonry (thk ≥ 175 mm)
  • in concrete (thk ≥ 140 mm)
  • in aerated concrete (thk ≥ 150 mm)
  • optional blunt installation in soffit
  • approved for installation at great heights (installation not at floor level: height on one or both sides > 500 mm above ground level - e.g. as manhole door/flap) with lower fire and smoke seal - also thresholdless
Optional
  • lock control
  • automated opening
  • motor locks ( also in 3-way locking)
  • powder coating in RAL colors
  • prison cell doors (special locking and food flap)
  • special solutions according to request and customer requirements

The information given refer to usual configurations. Subject to change without notice. No liability for incorrect information.

Individual configurations may be required when combining different performance characteristics.